Camps - Portable Water Treatment WATER TREATMENT
The WCC will operate automatically on a continuos basis without the need for continual supervision, and includes automatic control and monitoring systems for operation and water quality portability. The WCC automatically imparts a safe, measurable iodine biocide into the treated water ensuring that the water remains bacteriologically safe after treatment. No additional chemical dosing is required. "MODULAR" 20FT ISO CONTAINER
WATER (LIQUID {NON-FUEL}) STORAGE TANK. Capacity: 29/30,000 litres This unique MODULAR liquid storage ISO container can be sited just about anywhere and connected straight away ready for use. Used as a one-off 30,000 litre storage tank or connected in series side by side OR stacked two high, storing 100,000's of litres as required. International shipping standard (8 units high stackability for shipping/transportation). Rapid deployment in virtually any terrain - ideal for long or short term use. Modular ISO Water Storage Tank also available in 10ft (15,000 litre) and 40ft (61,000 litre) containers.
DIMENSIONS: Length 6.058 mm without connector box
The Equipment:
Pre-filter assembly comes fitted with standard 10, 5 and 1 µm filters. 1 off Automatic Water Quality Monitor with readout and shut down program plus visual and audio alarm. Central Control Panel with water failure and systems/pumps failure lights and alarms. Electrical distribution panel for external power supply
connection via socket or Buzz Bar terminal box arrangement. (State option.) Electrical connections and switching to immersion heaters (5KW each) 1 off in each external water holding tank. Internal air conditioning and heater assemblies to control WCC operational working temperatures.
Each Modular 100 is designed to purify up to 200,000 liters of water between changes. The Modular 100 incorporates filtration via carbon block filters, followed by purification via controlled release of a biocidal agent producing primary and secondary disinfection/purification. External Equipment Post filter sets per cold-water tap used for human consumption is mandatory. 3 sets are provided. Camps - Waste Water Management
Settled effluent is fed to the first stage of the biological reactor at a controlled rate. The influent is efficiently and quickly mixed with the aerated bulk liquid already present in the reactor. Air is pumped to the reactor through a fine bubble diffuser, suitably located in each chamber. The oxygen rich effluent comes into contact with the biomass attached to the surface of the structured media. Organic pollutants and oxygen rapidly diffuse into the biomass, where biological treatment takes place. The organic load applied to the media within the first and subsequent stages of the biological reactor is such as to ensure that the process kinetics are not oxygen limiting and are of the first order with respect to BOD removal. Contact Us: sales@rainbosupplies.com |


The
Water Control Center (WCC) is a fully automated, modular water treatment
system, within a self-contained, purpose fitted, 20ft ISO container,
which can treat and distribute water from any natural fresh water source.
Location:
Situated Under Ablutions Units
1
off 20ft I.S.O. container, fitted with 2 off pre-filtration assemblies,
3 off MODULAR 100 water purification skid mounted units (section 2.2),
including 2 off draw pumps with electronic program variability operating
in duty and standby mode. Plus 2 off, 30 litre per second combined,
distribution pumps with electronic program variability capable of setting